- Addressable device capacity: 2100 (IDP/SK) or 2032 (SD)
- AC Power: 120 VAC, 60 Hz, 5A or 240VAC, 50/60Hz, 2.8A
- Battery Charger Capacity: 17-55 AH
- Dimensions: 16.4” W x 26.4” H x 4.1” D (41.66cm W x 67.06cm H x 10.41cm D)
- UL Listed: S2766
Technical Specifications
System Capacity
- Intelligent Signaling Line Circuits: 1 (expandable)
- Addressable device capacity: 2100 (IDP/SK) or 2032 (SD)
- Programmable software zones: 999
- Output groups: 999
- Output circuits: 8 (expandable)
- SBUS devices: 63 (any combination)
Electrical
- AC Power: 120 VAC, 60 Hz, 5A or 240VAC, 50/60Hz, 2.8A
- Standby Current: 230 mA
- Alarm Current: 415 mA
- Flexput Circuits: Terminal block provides connections for (eight Class B or four Class A) NACs or auxiliary power. Power-limited, supervised circuitry. Maximum current per circuit: 3 A. Cannot exceed 9A total for all circuits. End-of-line resistor: 4.7k ohm, ½ watt for Class B NACs.
- Communication Loop: Supervised and power-limited, Class A or Class B, 32VDC, 150mA.
- Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.5 A @ 27.4 VDC (resistive), Form C.
- Battery: Cabinet holds a maximum of two 18AH batteries.
- Battery Charger Capacity: 17-55 AH.
Physical
- Dimensions: 16.4” W x 26.4” H x 4.1” D (41.66cm W x 67.06cm H x 10.41cm D)
- Weight: 33 lbs. (15 kg.)
- Color: Red or Black
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 – 49°C (32– 120°F) and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.
NFPA Standards
The IFP-2100 complies with the following standards and codes:
- NFPA 72
- NFPA 13
- NFPA 15
- NFPA 16
- NFPA 70
- UL 864 10th Edition
Agency Listings and Approvals
- UL Listed: S2766
- CSFM: 7165-0559:0505
- FDNY COA#: 6251
- FM Approved
- Seismic (CA): VMA-45894-05C