Simplex Network Card 4100-6078
- 18 AWG UTP Data Rate (baud): 9600
- 18 AWG UTP Distance: 17,000 ft (5.4 km)
- 24 AWG Telephone Cable UTP Data Rate (baud): 57.6 k
- Multi-mode Fiber Maximum Distance: 16400 ft (5 km)
- Single-mode Fiber Maximum Distance: 82000 ft (25 km)
Technical Specifications
Wire Size and Specifications
18 AWG Unshielded Twisted Pair (UTP):
- Maximum of 58 pF/ft. (190 pF/m) between conductors; shielded cable is allowed.
- Data Rate (baud): 9600
- Distance: 17,000 ft (5.4 km)
- Distance Note: Distance is with or without isolated loop protector or over-voltage protectors.
24 AWG Telephone Cable Unshielded Twisted Pair (UTP):
- Maximum of 22 pF/ft (72.2 pF/m) between conductors; overall shielded cable is allowed.
- Data Rate (baud): 57.6 k
- Distance: 10,000 ft (3 km)
24 AWG Telephone Cable Unshielded Twisted Pair (UTP):
- Maximum of 22 pF/ft (72.2 pF/m) between conductors; overall shielded cable is allowed.
- Data Rate (baud): 9600
- Distance: 12,000 ft (3.65 km)
24 AWG Telephone Cable Unshielded Twisted Pair (UTP):
- Maximum of 22 pF/ft (72.2 pF/m) between conductors; overall shielded cable is allowed.
- Data Rate (baud): 57.6 k
- Distance: 7,000 ft (2.13 km)
- Note: Shielded cable and circuit protection is required when wiring leaves the building.
Fiber TypeMulti-mode 50/125 or 62.5/125, numerical aperture = 0.275:
- MIFL: 1.5 dB/km at 1300nm
- Power Margin: 15 dB
- Safety Margin: -3 dB
- Maximum Distance: 16400 ft (5 km)
- Power Budget: 18 dB
- Coupler/Splice Loss: .75dB max for each mated pair connection; .30dB max for each fusion splice
Single-mode 9/125, numerical aperture = 0.2:
- MIFL: 1 dB/km at 1310nm
- Power Margin: 19 dB
- Safety Margin: -3 dB
- Maximum Distance: 82000 ft (25 km)
- Power Budget: 22 dB
- Coupler/Splice Loss: .75dB max for each mated pair connection; .30dB max for each fusion splice
Fiber Media Notes:
- Fiber Type for Duplex Fiber Optic: Cable specifications are for 50 or 62.5 micron core with 125 micron cladding multi-mode graded index fiber or 9micron core with 125 micron cladding single-mode fiber.78
- MIFL: Maximum individual fiber loss. Numbers shown are industry9 standard reference; refer to specific cable for exact specifications.10
- Distance: The maximum distance between nodes is determined by the total loss from the transmitter to the associated recei11ver (fiber loss, connector loss, splice loss and power margin), or the maximum distance listed, whichever is smaller.
- Power Budget: Use attenuation measurements at the following wavelengths: Multi-mode at 1300nm, Single-mode at 1310nm.