من السبت للخميس - من الساعة ٩ص حتى ٤ مساءاً

Dalton UPS B33

  • الكفاءة: وضع الخط (Line mode) ≥ 96%، الوضع الاقتصادي (ECO mode) ≥ 98%
  • وقت التحويل: 0 مللي ثانية
  • الهارمونك للجهد (THDV): ≤ 2% (حمل مقاوم)؛ ≤ 5% (حمل غير خطي)
  • الحد الأقصى لعدد الوحدات المتوازية: 6: 6
  • الحماية: دائرة قصر، حمل زائد، درجة حرارة زائدة، جهد زائد، جهد منخفض، جهد بطارية منخفض، وعطل المروحة
SKU:B33Categories:UPSTags:Battery, Charging, Phase, Power, Protection

المواصفات الفنية

Input
  • Rated Voltage: 380 V / 400 V / 415 VAC
  • Voltage Range:
    • 346 V ~ 456 V (full load)
    • 304 V ~ 346 V (Voltage rating 10%)
  • Rated Frequency: 50 / 60 Hz
  • Frequency Range: 50 / 60 Hz ± 5 Hz
  • Power Factor: ≥ 0.99
  • Total Harmonic Distortion (THDI): ≤ 3%
  • Input Current-Limiting: 1.1 times of rated current (0.1 ~ 1.1 settable)
  • Rectifier Delay Start: 10 s (1 ~ 300 settable)
Bypass
  • Bypass Voltage Range: ± 20% (settable)
Output (Inverter)
  • Rated Voltage: 380 V / 400 V / 415 VAC
  • Voltage Regulation: ± 1%
  • Frequency: Synchronized with utility in mains mode; 50 / 60 Hz ± 0.1% in battery mode
  • Waveform: Pure sinewave
  • Crest Factor: 3:1
  • Total Harmonic Distortion (THDV): ≤ 2% (Resistive load); ≤ 5% (non-linear load)
  • Transfer Time: 0 ms
  • Inverter Overload Capability:
    • Load ≤ 105%: long time work
    • 105% < load ≤ 110%: transfer to bypass in 60 min
    • 110% < load ≤ 125%: transfer to bypass in 10 min
    • 125% < load ≤ 150%: transfer to bypass in 1 min
    • 150% < load ≤ 200%: transfer to bypass in 200 ms
    • 200% < load: inverter off (UPS shutdown) in 100 ms and transfer to bypass output
  • Slight Adjustment of Inverter Output Voltage: ± 5 V
Battery
  • DC Voltage:
    • 10KVA To 40KVA: 240 VDC
    • 40KVA To 100KVA: 480 VDC
  • Number of Battery:
    • 10KVA To 20KVA: 40pcs 12V 9Ah
    • 30KVA, 40KVA: 60pcs 12V 9Ah
    • 60KVA To 100KVA: As Installed
  • Charging Current: Charging rate (settable) × battery capacity (settable) × number of battery group (settable)
  • Battery State Display: Battery remaining capacity and backup time
  • Battery Self Test: Settable periodic self-test; manually configurable test time and voltage
System Performance
  • Efficiency: Line mode ≥ 96%, ECO mode ≥ 98%
  • Max. Parallel Numbers: 6
  • Protections: Short-circuit, overload, over temperature, over voltage, under voltage, battery low voltage and fan failure
Communication & Display
  • Communications: RS232 / RS485 / dry contacts (standard), SNMP (optional)
  • IP Rating: IP 20
  • Display: 4.3 inches LCD touch screen (Optional)
Environmental
  • Operating Temperature: 0 ~ 40℃
  • Storage Temperature: – 25℃ ~ 55℃ (without battery)
  • Humidity: 0 ~ 95% (non-condensing)
  • Noise Level at 1 m: < 45 dB (< 55dB)