- Efficiency: Line mode ≥ 96%, ECO mode ≥ 98%
- Transfer Time: 0 ms
- Total Harmonic Distortion (THDV): ≤ 2% (Resistive load); ≤ 5% (non-linear load)
- Max. Parallel Numbers: 6
- Protections: Short-circuit, overload, over temperature, over voltage, under voltage, battery low voltage and fan failure
Technical Specifications
Input
- Rated Voltage: 380 V / 400 V / 415 VAC
- Voltage Range:
- 346 V ~ 456 V (full load)
- 304 V ~ 346 V (Voltage rating 10%)
- Rated Frequency: 50 / 60 Hz
- Frequency Range: 50 / 60 Hz ± 5 Hz
- Power Factor: ≥ 0.99
- Total Harmonic Distortion (THDI): ≤ 3%
- Input Current-Limiting: 1.1 times of rated current (0.1 ~ 1.1 settable)
- Rectifier Delay Start: 10 s (1 ~ 300 settable)
Bypass
- Bypass Voltage Range: ± 20% (settable)
Output (Inverter)
- Rated Voltage: 380 V / 400 V / 415 VAC
- Voltage Regulation: ± 1%
- Frequency: Synchronized with utility in mains mode; 50 / 60 Hz ± 0.1% in battery mode
- Waveform: Pure sinewave
- Crest Factor: 3:1
- Total Harmonic Distortion (THDV): ≤ 2% (Resistive load); ≤ 5% (non-linear load)
- Transfer Time: 0 ms
- Inverter Overload Capability:
- Load ≤ 105%: long time work
- 105% < load ≤ 110%: transfer to bypass in 60 min
- 110% < load ≤ 125%: transfer to bypass in 10 min
- 125% < load ≤ 150%: transfer to bypass in 1 min
- 150% < load ≤ 200%: transfer to bypass in 200 ms
- 200% < load: inverter off (UPS shutdown) in 100 ms and transfer to bypass output
- Slight Adjustment of Inverter Output Voltage: ± 5 V
Battery
- DC Voltage:
- 10KVA To 40KVA: 240 VDC
- 40KVA To 100KVA: 480 VDC
- Number of Battery:
- 10KVA To 20KVA: 40pcs 12V 9Ah
- 30KVA, 40KVA: 60pcs 12V 9Ah
- 60KVA To 100KVA: As Installed
- Charging Current: Charging rate (settable) × battery capacity (settable) × number of battery group (settable)
- Battery State Display: Battery remaining capacity and backup time
- Battery Self Test: Settable periodic self-test; manually configurable test time and voltage
System Performance
- Efficiency: Line mode ≥ 96%, ECO mode ≥ 98%
- Max. Parallel Numbers: 6
- Protections: Short-circuit, overload, over temperature, over voltage, under voltage, battery low voltage and fan failure
Communication & Display
- Communications: RS232 / RS485 / dry contacts (standard), SNMP (optional)
- IP Rating: IP 20
- Display: 4.3 inches LCD touch screen (Optional)
Environmental
- Operating Temperature: 0 ~ 40℃
- Storage Temperature: – 25℃ ~ 55℃ (without battery)
- Humidity: 0 ~ 95% (non-condensing)
- Noise Level at 1 m: < 45 dB (< 55dB)
Necessary cookies enable essential site features like secure log-ins and consent preference adjustments. They do not store personal data.
None
Functional cookies support features like content sharing on social media, collecting feedback, and enabling third-party tools.
None
Analytical cookies track visitor interactions, providing insights on metrics like visitor count, bounce rate, and traffic sources.
None
Advertisement cookies deliver personalized ads based on your previous visits and analyze the effectiveness of ad campaigns.
None
Unclassified cookies are cookies that we are in the process of classifying, together with the providers of individual cookies.
None